The PSS-GLAP series 2/4/6/8 Zone gas leakage alarm panel is designed based on ERTL standard. And it is the central part of a gas leakage alarm system, designed for applications requiring a gas leak detector, manual call point, and hooter. Each zone can be disabled by a button.
Maximum number of Gas Leak Detector Inputs: 2 detectors each zone
Available Options: 2-4 Zone, 6-8 Zone
Outputs for Alarm devices: Includes 2 bells/fire relay/ fault relay
Auxiliary resettable power output: 24VDC/ 100mA limiting protection
Automatic power switchover: mains power and secondary power (from batteries)
Independent functional buttons with indication: User friendly interface for easy operation and recognition
Access levels to enter the panel
Fault supervision and notification: inputs, outputs, system, power, earth, fuse
Disablement: zones disablement
Evacuation: Fire drills to simulate leak alarm condition on panel
Silence: sounders and buzzer silence
Speak to our fire safety expert to learn more about this product.
1 | AC INPUT | 220VAC 50/60Hz (+ 10% - 15%) |
2 | DC OUTPUT | 24VDC typical (+10% - 15%) |
3 | Voltage for MCU | 5V for MCU |
4 | Current at 24VDC from PSE | 450mA standby current |
5 | Maximum current from PSE | 1A except batteries charge |
6 | Batteries current | 1.85A maximum, current limited |
7 | Auxiliary output | 24VDC +/- 10%, 100 mA max, current limited, monitored |
8 | Batteries | 2*12V/ 7Ah sealed lead acid gel, self-regulated * |
9 | Battery low-voltage protection | 21V |
10 | Detectors connection allowed each zone | 20 (except MCPs) |
11 | Zone alarm current | 6mA minimum/ 27mA maximum |
12 | Sounder output | 2*0.75A |
13 | Fire Relay | 1A/30VDC maximum |
14 | Fault Relay | 1A/30VDC maximum |
15 | Communication protocol | 2 wires RS485 bus system |
16 | Fuse for AC Power | 1 A/ 250V glass tube fuse 5 X 20mm |
17 | Fuse on DC Power | 1A/ 250V glass tube fuse 5 X 20mm |
18 | Environmental | Class A temperature range: -5 to 40°C (23~104°F) Humidity: 5 to 95% RH, non-condensing |
19 | Terminal blocks rating | All terminals rated for 12 to18 AWG (0.75 to 2.5 mm2) |